44 KENR8601
Systems Operation Section
(Table 7, contd)
OP5-1 Setpoints
(1)
- Protective Relaying Pro g ramming
Setpoint
Name Description
Range Of Value
Factory
Default
P135
Phase Overcurrent
Shutdown Time Delay
Amount of time the GSC+P waits
before issuing a phase overcurrent
shutdown.
0to250seconds
(2)
in increments
of 1
30
seconds
P136
Total Ove r c u r r
ent
Shutdown Threshold
Level of curren
ttheGSC+Pusesto
issue a total overcurrent shutdown.
100 to 160% of th
ree times
nameplate current in increments
of 5%
110%
P137
Total Overcurrent
Shutdown Time Delay
Amount of time the GSC+P waits
before issuing a total overcurrent
shutdown.
0to250second
s
(2)
in increments
of one .
30
seconds
P138 KW Level Relay
Enable
The GSC+P ena
bles or disables the
kW level relay function.
0 - disabled
1 - enabled
1
P139 KW Level Relay
Threshold
Level of power the GSC+P uses to
activate the kW level relay function.
0to110%ofnameplatepowerin
increments of 1%
105%
P140 KW Level Relay Time
Delay
Amount of time the GSC+P waits
before activating the kW relay function.
0to120seconds
(2)
in increments
of 1
0
seconds
P141 KW Level Rela
y
Disengage Threshold
Level of power the GSC+ P uses
deactivate the kW level relay function.
0to110%ofnameplatepowerin
increments of 1%
100%
P142 KW Level Relay
Disengage Time D elay
Amount of time the GSC+P waits
before deac
tivating the kW level relay
function.
0to120seconds
(2)
in increments
of 1
10
seconds
(1)
The setpoints are programmed at the factory to the default value. The setpoints may be changed in order to satisfy customer or application
requirements.
(2)
When programmed to 0 seconds, the actual time is from 0.5 to 1.0 seconds.
i02898425
AC Factory Calibration
Setpoint Programming OP5-2
SMCS Code: 4490
The AC Fact
ory Calibration Setpoints (OP5-2) are
only us ed in the factory. The setpoin ts are rea d only
and the setpoints a re not accessible by the user.
i02896713
Parallel
Setpoint Programming
OP5-3
SMCS Code
: 4490
The Synchronization setpoints within the GSC+P
define var
ious parameters that allow precise
frequency and phase matching.
The setpoints are programmed (set) in the GSC+P
at the fact
ory to the default values that are in the
following chart. The setpoints may be changed to
satisfy the requirements of the customer. Also the
setpoint
s may be changed to satisfy the requirements
of the application.