78 KENR8601
Troubleshooting Section
Te st Step 2. CHECK THE FUSES.
A. Check the three fuses on the AC Transformer Box
+(ATB+).
Expected Result:
The fuses should not be open.
Results:
•
OK – The fuses are not open. Proceed to Test
Step 3.
•
NOT O K – One or more of the fuses are open.
Repair: One or more of the fuses are open. Check
for a shorted component or damaged wiring.
Troubleshoot and repair the problem. Refer to
the Ge ne r ator Set Wiring Diagram in Testing And
Adjusting, “Schematics And Wiring Diagrams”.
After the problem has been repaired, replace the
fuses.
STOP.
Te st Step 3. CHECK THE GENERATOR
OUTPUT.
A. Open the circuit brea ker o r remove the load.
B. Start the engine and run the genset.
C. Measure the voltage between all three fuses on
the ATB+.
Expected Result:
The line to lin e voltage should measure the rated
voltage of the genset.
Results:
•
OK – The voltages are correct and the problem
remains. Proceed to Test Step 4.
•
NOT OK – One or more of the voltages are NOT
correct.
Repair: The wiring or the connections are
damaged. Check for damaged wiring between
the ATB+ and the bus. Refer to the Gene rator
Set Wiring Diagram in Testing And Adjusting,
“Schematics And Wiring Diagrams”. Also, check
the electrical connections at the terminal of the
ATB+ . Refer to Testing And Adjusting, “Ele ctrica l
Connector - Inspect”.
STOP.
Test Step 4. CHECK THE CONNEC TIONS
A. Shut down the engine.
B. Check the harness connector and the terminals of
the ATB+.
C. Check the GSC+P harness connector. Refer to
Testing And Adjusting, “Electrical Connector -
Inspect”.
D. Check for one or m ore damaged wires between
the ATB+ and the GSC+P. R efer to the G e nerator
Set Wirin g Diagram in Tes tin g And Adjusting,
“Schematics And Wiring Diagrams”.
Expected Result:
The wiring and the connectors should have been
good.
Results:
•
OK – NO problem was found with the connectors
or with the wiring. Proceed to Test Step 5.
•
NOT OK – The problem was w ith the connectors
or with the wiring.
Repair: Repair the connectors or replace the
wiring harness.
STOP.
Test Step 5. CHECK THE OU T PU TS OF
THE ATB+
A. Remove the GSC+P harness connector from the
ATB+.
B. At the terminal of the ATB+ , measure the
resistance b et ween the following terminals:
terminal J1-7 to terminal J1-1, terminal J1-7 to
terminal J1-2, and terminal J1-7 to terminal J1-3
Expected Result:
Each of the resistance measurements should be 7.0
±1.0Ohms.
Results:
•
OK – E ach of the resistance measureme nts is 7.0
± 1.0 Ohms. Proceed to Test Step 6.
•
NOT OK – One o r more of the resistance
measurements is NOT 7.0 ± 1.0 O hms.