KENR8601 83
Troubleshooting Section
Expected Result:
The p ower consu mption that is displa yed on t he
GSC+P should be accurate.
Results:
•
OK – The power consumption that is displayed on
the GSC+P is accurate.
Repair: There is no problem at this time. Keep
monitoring the system for inaccurate readings.
STOP.
•
NOT OK – The power consumption that is
displayed on the GSC+P is NOT accurate. Proceed
to Test Step 10.
Te st Step 4. CHECK SETPOINT P020
A. Check the setpoint P020. Refer to Testing and
Adjusting, “Engine/Generator Setpoint Viewing
OP2-0”.
Expected Result:
P020 should be set to match the system’s application.
To find the correct setpoint, refer to Table 17 .
Results:
•
OK – Setpoint P020 is set for the application.
Proceed to Test Step 5.
•
NOT OK – Setpoin t P020 is NOT set for the
application.
Repair: Program P020 to match the system’s
application. Refer to Testing and Adjusting,
“Engine/Generator Setpoint Programming OP5-0”.
STOP.
Te st Step 5. CHECK THE JUMPER FOR
CORRECT INSTALLAT ION
A. Check the setpoint P020. Refer to Testing and
Adjusting, “Engine/Generator Setpoint Viewing
OP2-0”.
B. Check the jumper on the relay module for correct
AC voltage range. Refer to System Operation,
“AC Voltage Range - Adjust”.
Expected Result:
The jumper should be insta lled correc tly in order to
match the value in setpoint P020.
Results:
•
YES – The jump e r is installed correc tly in order
to match the value in setpoint P020. Proceed to
Test S t e p 6.
•
NO – T he jumper is NOT installe d correctly in
order to match the value in setpoint P020.
Repair: Install the jumper in accordance to the
procedure in System Operation, “AC Voltage
Range - Adjust”.
STOP.
Test Step 6. CHECK THE VALUES IN OP8
A. Turn the ECS to the STOP position in order to
shut down the engine. Enter service mode and
enter the password.OP4 is showing on the lower
display of the GSC+P. For more information, refer
to Systems Operation, “Service Mode”for m ore
information. Refer to the Systems Operation,
“Password Entry OP3”for more information.
B. Press the “SCROLL UP” key five times. “OP 8” is
showing on the lower display.
C. Press the “SCROLL UP” key five times. “OP 8” is
showing on the lower display.
D. Press the “SELECT” key. “AC01” is showing. The
value of the setpoint is also showing. The value
will be between 0 to 255. R ecord the value.
E. Press the “SCROLL UP” key in order to retrieve
the values for the setpoints AC02 through AC06.
Record each value.
F. Press the “EXIT” key. “OP 1” is showing on the
lower displa y.
G. Press the “EXIT” key. The display will return to the
Normal M o de .
H. Compare the recorded values with the values that
are written on the bar code sticker of the ATB+.
Expected Result:
The recorded values should match the values that
are written on the bar code sticker of the ATB+.
Results:
•
Yes – The values match. Proceed to Test Step 7.
•
NO – The values do NO T match.