SEBU8219-01 49
Operation Section
Features and Controls
i02443021
Electron ic Modular Co nt r ol
Panel 3 (EMCP 3
)
SMCS Code: 4490
Electronic Control Modu le
(Generator Set)
g01045431
Illustration 50
(1) Display screen
(2)ACoverviewkey
(3) Engine overview key
(4) Yellow w arning lamp
(5) Red shutdown lam p
(6) Alarm ac knowledge key
(7) Lamp test key
(8) Run key
(9) Auto key
(10) Stop key
(11) Up ke y
(12) Escape key
(13) Right key
(14) Enter key
(15) Down key
(16) Left key
Navigation Keys
AC Overview (2) – The “AC OVERVIEW” key
will navigate the display to the first screen of AC
information. The “AC OVERVIEW” information
contains various AC parameters that summarize the
electrical operation of the generator set.
Engine Overview (3) – The “ENGINE OVERVIEW”
key will navigate the display to the first screen of
engine information. The “ENGINE OVERVIEW”
information contains various engine parameters that
summarize the operation of the generator set.
Acknowledge Key (6) – Pressing the
“ACKNOWLED GE ” key will cause the horn
relay to turn off. This will silence the horn. Pressing
this key will also cause any red or yellow flashing
lights to either turn off or to come on continuously,
depending on the active status of the alarms. The
“ACKNOWLEDGE” key may also be configured
to send out a global alarm silence signal on the
J1939 Data Link, which will silence the horns on the
annunciators.
Lamp Test Key (7) – Pressing and holding the
“LAMP TEST” key will cause each LED and the
display screen pixels to turn on continuously until the
key is released.