SEBU8219-01 75
Maintenance Section
Maintenance Recommendations
i02364500
Gen erator St art-up C hecklist
SMCS Code: 4450
Table 8
GENERATOR START-UP CHECKLIST
RATING INFORMATION
Engine Serial Number: ___________________________________
Arrangement Number: ___________________
Generator Serial Number: _________________________________
Arrangement Number: ___________________
GENERATOR NAME PLATE INFORMATION
Voltage: ___________________
Package (prime, continuous, standby): _________________
Amperage: _________________ Kilowatts: ________________________________________
Storage Location:
Main Stator M
egohmmeter Reading:
Before Stora
ge:
After Storag
e:
Generator dried for 24 hours prior to start-up? (Y/N)
Drying method:
SPACE HEATERS
Yes No
Comments
Space heaters operating properly?
Space heater operated 48 hours before
start-up?
MEGOHMMETER TEST (“SEHS9124”) 30 sec.
reading
60 sec.
reading
30 sec.
corrected
60 sec.
corrected
Ambient
temp.
Comments
Main Stator
Main Rotor
Exciter Stator
Exciter Rotor
Beginning
of Storage
PMG Stator
Main Stator
Main Rotor
Exciter Stator
Exciter Rotor
Start-up
PMG Stator
Regulator Voltage Amps
Comments
“T1” to “T2” AC
“T1” to “T3” AC
“T2” to “T3” AC
“11” to “12” AC
“11” to “13” AC
No Load
“12” to “13” AC
(continued)